On November 22, 2016, a high-pressure isobutane release occurred in the sulfuric acid alkylation unit at the ExxonMobil Refinery in Baton Rouge, Louisiana, during minor maintenance on a flammable isobutane line. A small bore threaded pipe fitting failed, releasing isobutane that ignited -- seriously injuring four workers and injuring two others.
The CSB issued a Safety Bulletin rather than a full investigation report. The bulletin addressed the hazards of small bore threaded piping in high-pressure flammable service and the critical importance of rigorous de-inventorying procedures before maintenance. No formal CSB recommendations with response obligations were issued; the Safety Bulletin communicated lessons for industry-wide awareness.
Key Safety Bulletin lessons: small bore threaded connections in high-pressure flammable service are susceptible to failure and should be minimized or replaced with welded alternatives; de-inventorying procedures before maintenance on flammable lines must be rigorous and step-by-step verified; atmospheric flammable gas monitoring must be performed before opening any process connections; and workers must not be positioned in the direct release zone during maintenance on flammable process equipment.
This incident traced to breakdowns across 3 PSM elements (SOP · MI · HOW). Each represents a documented gap that process safety documentation and consulting can close before a similar event occurs at your facility.