On June 9, 2009, four workers were fatally injured and dozens of others were injured when a natural gas explosion occurred at the ConAgra Foods Slim Jim manufacturing facility in Garner, North Carolina. The explosion occurred during maintenance on a natural gas distribution line inside the building -- specifically, during the process of purging the gas piping to remove air before returning it to service.
CSB investigation found that gas piping was being purged by releasing natural gas into the interior of the building, rather than venting it safely outdoors. The purged gas accumulated to an explosive concentration inside the occupied facility and ignited. The applicable natural gas code at the time (NFPA 54/National Fuel Gas Code) did not explicitly prohibit indoor purging of gas piping -- an omission the CSB found to be a critical regulatory gap.
The CSB issued 4 urgent recommendations to the National Fire Protection Association (NFPA), American Gas Association (AGA), and International Code Council (ICC) to immediately prohibit indoor purging of fuel gas piping and require outdoor venting in revised editions of the National Fuel Gas Code and International Fuel Gas Code. All four recommendations were implemented. The case remains one of the clearest examples of a fatal incident resulting from a gap in a national gas code.
This incident traced to breakdowns across 3 PSM elements (SOP · TRN · HOW). Each represents a documented gap that process safety documentation and consulting can close before a similar event occurs at your facility.