→ Gold Creek Foods
Include provisions in the emergency action program for informing local emergency responders about hazardous substances (including liquid nitrogen), the location of emergency-critical equipment, and facility drawings. [Closed: Acceptable Action]
→ Messer LLC (Supplier)
Update the product stewardship policy to include Messer participation in customers' PHAs before cryogenic freezing startup, verification of CGA P-76 signage, and siting review of emergency shutoff devices. [Closed: Exceeds Recommended Action]
→ Messer LLC (Supplier)
Create an informational product for customers on the safety issues in the report, recommending safety management systems for inert gas asphyxiation hazards based on CGA guidance. [Closed: Acceptable Alternative Action]
→ OSHA
Update the Region 4 Poultry Processing Facilities Regional Emphasis Program to explicitly cover liquid nitrogen freezing processes.
→ OSHA
Update the Region 5 Regional Emphasis Program for the Food Manufacturing Industry to explicitly cover liquid nitrogen freezing processes.
→ OSHA
Update the Region 6 Poultry Processing Facilities Regional Emphasis Program to explicitly cover liquid nitrogen freezing processes.
→ OSHA
Promulgate a standard specific to cryogenic asphyxiants covering equipment design, indoor atmospheric monitoring, emergency shutdown, training, emergency action plans, and PSM elements.
→ OSHA
Develop and publish a guidance document on process safety management practices for processes handling compressed gases and cryogenic asphyxiants.
→ Compressed Gas Association (CGA)
Develop a comprehensive standard for safe storage, handling, and use of liquid nitrogen in stationary applications, including atmospheric monitoring, alarms, ventilation, and emergency shutdown device locations.
→ Compressed Gas Association (CGA)
Update CGA P-76 to require atmospheric monitoring with distinct visible and audible alarms, remotely operated emergency isolation valves, and guidance on safe location of emergency stop devices.
→ NFPA
Update NFPA 55 to require atmospheric monitoring with cryogenic asphyxiants and to include guidance on safe location of manual shutoff valves and emergency push buttons.
→ International Code Council (ICC)
Update the International Fire Code to require atmospheric monitoring with cryogenic asphyxiants and to include guidance on safe location of shutoff devices for cryogenic fluid service.
Full recommendation text and current status: CSB investigation page.