On April 8, 2021, an explosion and fire at the Yenkin-Majestic paint and OPC Polymers Corporation resin plant in Columbus, Ohio, fatally injured one employee and sent eight others to area hospitals. A low-pressure process vessel (below 15 psig) failed due to an unauthorized alteration — the vessel had been modified without a formal engineering design review or pressure test — releasing flammable vapors that ignited as a vapor cloud explosion.
The CSB found that low-pressure process vessels (below 15 psig) containing flammable chemicals at Yenkin-Majestic were not covered by the ASME Boiler and Pressure Vessel Code, had no formal mechanical integrity program, and lacked required documentation. The facility had no flammable gas detection, no flame-resistant (FR) clothing requirements, and had resisted implementing CSB recommendations post-incident — all seven recommendations remain open.
This incident traced to breakdowns across 1 PSM element (PHA). Each represents a documented gap that process safety documentation and consulting can close before a similar event occurs at your facility.