On April 3, 2017, a semi-closed receiver (SCR) steam condensate pressure vessel at the Loy Lange Box Company manufacturing facility in St. Louis, Missouri, exploded violently. The vessel became airborne and crashed through the roof of an adjacent business, killing four people — one Loy Lange employee and three members of the public. The failure was a BLEVE resulting from years of unmitigated corrosion.
The CSB investigation found a cascade of failures: Kickham Boiler attempted a repair in 2012 but left damaged material in place. Arise Boiler Inspection issued a certificate accepting the inadequate repair without verifying its quality. The City of St. Louis missed multiple inspection opportunities. Loy Lange had no formal mechanical integrity program.
The August 2022 CSB report issued 7 recommendations to Loy Lange, Kickham Boiler, Arise Boiler Inspection, the National Board of Boiler and Pressure Vessel Inspectors, and the City of St. Louis — focused on inspection quality, repair verification, and third-party inspector accountability.
This incident traced to breakdowns across 2 PSM elements (MI · PSI). Each represents a documented gap that process safety documentation and consulting can close before a similar event occurs at your facility.