On April 3, 2017, a semi-closed receiver (SCR) steam condensate pressure vessel at the Loy Lange Box Company manufacturing facility in St. Louis, Missouri, catastrophically failed at its bottom head, causing a boiling liquid expanding vapor explosion (BLEVE). The blast fatally injured a Loy Lange stationary engineer working nearby and launched the vessel about 520 feet through the air and through the roof of the Faultless Healthcare Linen building, fatally injuring three of its employees. Oxygen pitting and general corrosion had thinned the bottom head to as little as 0.012 inches, and Loy Lange had continued operating the vessel after a leak was observed the previous Friday.
The CSB investigation found a cascade of failures: Kickham Boiler attempted a repair in 2012 but left damaged material in place. Arise issued a certificate accepting the inadequate repair without verifying its quality. The City of St. Louis missed multiple inspection opportunities. Loy Lange had no formal mechanical integrity program.
The August 2022 CSB report issued 8 recommendations to Loy Lange, the City of St. Louis Board of Aldermen, the Mayor of St. Louis, the inspection company Arise, and the National Board of Boiler and Pressure Vessel Inspectors. Louis — focused on inspection quality, repair verification, and third-party inspector accountability.
Full recommendation text and current status: CSB investigation page.
See this vessel worked through a HAZOP, deviation by deviation: A HAZOP Node, Worked Line by Line →
This incident traced to breakdowns across 2 PSM elements (MI · PSI). Each represents a documented gap that process safety documentation and consulting can close before a similar event occurs at your facility.