On August 29, 2017, Hurricane Harvey made landfall and the unprecedented flooding that followed disabled all refrigeration systems at the Arkema Inc. chemical plant in Crosby, Texas. The plant manufactures organic peroxides -- thermally unstable chemicals that spontaneously combust when they exceed their control temperatures. Without refrigeration, the peroxides began to heat; on August 31 the first trailer caught fire. Officials intentionally ignited the remaining trailers on September 3, 2017.
The 1.5-mile evacuation zone displaced thousands of residents. Twenty-one first responders were treated after exposure to chemical smoke. The CSB found that Arkema's facility flood hazard assessment did not evaluate the risk of floodwaters disabling critical safeguards such as backup power and refrigeration, and that no adequate independent layer of protection existed to maintain refrigeration capability during a major flood event.
The May 2018 final report issued 5 recommendations to Arkema's Crosby facility, Arkema Inc. corporate, the Center for Chemical Process Safety (CCPS), and Harris County, Texas. All 5 recommendations were closed.
This incident traced to breakdowns across 4 PSM elements (PHA · MI · EAP · PSI). Each represents a documented gap that process safety documentation and consulting can close before a similar event occurs at your facility.