At about 6:15 p.m. on March 4, 1998, a vessel catastrophically failed and a fire broke out at the Temple 22-1 Common Point Separation Facility near Pitkin, Louisiana, owned by Sonat Exploration Co. Four workers near the vessel were killed, and the facility was significantly damaged.
The vessel lacked a pressure relief system and ruptured from overpressure during startup, releasing flammable material that ignited. The CSB's recommendations addressed design review, pressure relief for all equipment exposed to overpressure, and written startup and purging procedures with training for all workers, including contractors.
The CSB approved its final report on September 21, 2000, with 5 recommendations.
Full recommendation text and current status: CSB investigation page.
This incident involved breakdowns across 4 PSM-related areas (PHA · SOP · TRN · PSSR). Each represents a gap that process safety programs are designed to close.