At about 2:45 a.m. on November 22, 2006, an explosion destroyed the CAI and Arnel facility in Danvers, Massachusetts. A CAI ink-mixing tank containing flammable heptane and alcohol solvents had been left heating overnight. It overheated, releasing vapor that filled the building and ignited. The blast wave damaged or destroyed dozens of nearby homes and businesses in the Danversport neighborhood.
The CSB found that CAI lacked safeguards, such as alarms and automatic shutoffs, that would have prevented the mixture from overheating while unattended. Based on the quantities of flammable materials it used, CAI was required to comply with OSHA's PSM standard. The facility was licensed for 6,000 gallons, but stored more than 20,000 gallons of flammable liquids and more than 50,000 pounds of nitrocellulose, and the fire department had not inspected it in more than four years.
The CSB also found that national model fire codes did not provide enough safeguards for flammable liquids heated inside buildings. The final report was approved May 13, 2008, with 11 recommendations.
Full recommendation text and current status: CSB investigation page.
This incident involved breakdowns across 4 PSM-related areas (PHA · SOP · MI · PSI). Each represents a gap that process safety programs are designed to close.