On August 28, 2016, a nitrous oxide explosion at the Airgas facility in Cantonment, Florida, near Pensacola, killed one worker. Nitrous oxide can decompose violently.
The CSB noted that safety management system and regulatory deficiencies contributed to the incident. Its recommendations point to the issues: a nitrous oxide pump run-dry shutdown interlock that should be designed to the ISA-84 safety instrumented systems standard, strainers used as flame arrestors that needed testing under realistic conditions, the lack of a safety management system standard for nitrous oxide manufacturing, and pump literature that did not warn about decomposition hazards.
The CSB released its final report on April 20, 2017, with 6 recommendations. After the incident, Air Liquide began a comprehensive review of its nitrous oxide production facilities, trucking fleet, and cylinder filling.
Full recommendation text and current status: CSB investigation page.
This incident involved breakdowns across 4 PSM-related areas (PHA · MI · PSI · SOP). Each represents a gap that process safety programs are designed to close.