On April 9, 1998, a propane boiling liquid expanding vapor explosion (BLEVE) at the Herrig Brothers Farm in Albert City, Iowa killed two volunteer firefighters and injured seven others. An all-terrain vehicle (ATV) had struck and damaged the piping connected to a 30,000-gallon propane storage tank on the farm property, releasing liquid propane that ignited and began burning. When the volunteer fire department arrived to fight the fire, the burning propane tank catastrophically failed — a BLEVE — launching tank fragments and a fireball that killed the two firefighters.
The ATV had struck a propane fill pipe connected to the large storage tank, shearing the pipe and initiating the propane release and fire. The fill pipe lacked an excess flow valve or other automatic shutoff that would have stopped the propane flow when the pipe was sheared. The volunteer firefighters who responded were not adequately trained on the behavior of propane BLEVEs or the standoff distance required to survive a propane tank BLEVE event.
The CSB investigation found that the absence of an excess flow valve on the propane fill pipe was the primary enabling factor for the sustained propane release. In addition, the local volunteer fire department lacked training specific to propane BLEVE hazards and did not maintain the standoff distance that would have protected firefighters from the tank failure. The case underscores the importance of both mechanical safeguards on propane systems and emergency responder training on BLEVE behavior.